Product Description
Application: | Designed for use with liquids and gases, refrigerants (R717, HCFC, HFC and HC) in explosive areas |
Range: | 0.5 ÷ 4 bar |
Differential: | 0.3 bar |
Max. operating pressure: | 22bar |
Reset function: | AUTO |
Output: | 1 x SPDT |
Contact load: | Ui: 29V, Ii:0.5A, Pi: 1W |
Ambient temperature: | -20 ÷ 65ºC |
Materials: | see data sheet |
Process connection: | 2 x G3/8" + welded nipple ø6.5/10 mm |
Cable entry: | 2 x Pg13.5 (6 ÷ 14mm) |
Protection class: | IP66 |
Approvals: | CE, ATEX 1406X (Ex II 2G, Exia IIC T6...T1 Gb) |