Product Description
Application: | designed to use for conversion of mA, V, RTD, Lin R, TC, Potm signals to analogue mA, V signals |
Number of channels: | 1 |
Functions: | process callibration signal simulation password protection error diagnostics programmable detachable display 4501 |
Mounting: | DIN rail (35mm) |
Input: | RTD: - 200 ÷ 850ºC TC: -200 ÷ 2300ºC Lin R: 0 ÷ 10kΩ Potm: 10Ω ÷ 100kΩ mA: 0/4 ÷ 20mA (±23mA) V: 0/0.2 ÷ 1, 0/1 ÷ 5, 0/2 ÷ 10 VDC (±12V) |
Output: | mA: 0/4 ÷ 20 mA / Namur NE43 (3.5/23mA) direct or iverted V: 0 ÷ 10VDC (programmable ranges) |
Temperature Compensation: | for Internal CJC remember to order CJC connectors: 5910 (ch. 1) or 5930 (ch. 2) |
Supply voltage: | 21.6 ÷ 253 VAC / 19.2 ÷ 300VDC |
Accuracy: | ±0.1% of span |
Isolation voltage: | 2.3 kVAC |
Response time: | temperature: ≤ 1sec mA/V: ≤ 400ms |
Ambient temperature: | -20 ÷ 60ºC |
Programming: | PR4501 display, LCD, 4 lines |
Protection class: | IP20 |
Dimensions (H x W x D): | 109 x 23.5 x 104 mm |
Weight: | 155gr |
Approvals: | SIL, DNV (marine), UM, FL |