Product Description
Application: | designed to measure input AC current and voltage signals and convert it on the output to active or passive ±mA/V signals |
Number of channels: | 1 |
Functions: | the 0 ÷ 5 AAC RMS range makes it possible to accurately measure a typical current transformer the 0 ÷ 300 VAC RMS range allows accurate supply voltage monitoring converts narrow AC current / voltage inputs to wide bipolar or unipolar outputs, e.g. 0 ÷ 1 VAMS input = ±10 volt or 4...20 mA output with a minimum span of 0.5 AAC RMS or 0.5 VAC RMS process callibration (2-points) programmable detachable display 4501 |
Mounting: | DIN rail (35mm) |
Input: | ~A: 0 ÷ 5AAC / 40 ÷ 400Hz (programmable ranges: 0 ÷ 0.5 / 1 / 2.5 / 5 AAC) ~V: 0 ÷ 300VAC / 40 ÷ 400Hz (programmable ranges: 0 ÷ 0.5 / 1 / 2.83 / 5 / 120 / 230 / 300 AAC) |
Output: | mA active (unipolar/bipolar): 0/4 ÷ 20 mA (±10 / ±20mA) / Namur NE43 (3.5/23mA) direct or iverted mA passive (2-wire): 0/4 ÷ 20mA (supply voltage: 3.5 ÷ 30VDC) direct or iverted current output: 0 ÷ 23mA (±23mA) V: 0 ÷ 10VDC (programmable ranges: 0/0.2 ÷ 1; 0/1 ÷ 5; 0/2 ÷ 10, 1 ÷ 0.2/0; 5/1 ÷ 0; 10 ÷ 2/0 V) |
Supply voltage: | 21.6 ÷ 253 VAC / 19.2 ÷ 300VDC |
Accuracy: | ±0.3% of selected range |
Isolation voltage: | 2.3 kVAC |
Response time: | 0 ÷ 60sec |
Ambient temperature: | -20 ÷ 60ºC |
Programming: |
PR4501 display, LCD, 4 lines |
Protection class: |
IP20 |
Dimensions (H x W x D): |
109 x 23.5 x 104 mm |
Weight: |
155gr |
Approvals: |
SIL2, UL |